6.1.4

Parameter window "Heating control"

Status send heat requirement
Options:
- Yes
- No
If you set the "Status send heat requirement" to "yes", the ambient temperature controller will send an ON telegram
via the relevant 1-bit communication object once it is in heating mode. If the room thermostat is in the "dead zone"
between heating and cooling or in cooling mode, the thermostat sends an OFF telegram via the status heating object.
This parameter is only available if the "Heating" or "Heat and cool" control functions are set.
Cycle time heating control value sending (0 - inactive, min)
Options:
- 0
- 1
- ...
- 60
The room thermostat can send the control value, even if the value remains unchanged. This is often required since
the connected actuator otherwise assumes that the room thermostat is no longer available. This enables the actuator
to activate its force-position control, which is only deactivated when a new control value is received.
The cycle time for automatic sending of the control value is adjustable from 1 to 60 min. Cyclic sending can also be
disabled (setting 0).
This parameter is only available if the "Heating" or "Heat and cool" control functions are set.
Control mode
Options:
- 2-step
- PWM
- Continuous
- Fan Coil
26 Commissioning | MYLOS
Building Automation
®
Commissioning