Honeywell UDC2800 Product Manual page 99

Universal digital controller
Hide thumbs Also See for UDC2800:
Table of Contents

Advertisement

Sensor Type
RTD Pt500
TC PR40-PR20
Linear
Milliamps
Millivolts
Volts
Carbon Oxygen
*    The Factory Calibrated millivolt values for the Thermocouple
Differential Input are for a pair of J thermocouples at an ambient
temperature mean of 450°F / 232°C.  Other thermocouple types and
ambient temperature means may be accomplished via Field
Calibration of the input, with the range value limits being –4 mV to
+16 mV for the zero and span values. See Input 1 Set up Wiring for
procedure.
**    The range values for Radiamatic Type RI are customer
configurable.
Chapter 6 -  Input Calibration
PV Input
Range Values
Range
°F
°C
0%
to
to 649
ohms
1200
–300
–184
126.012
to
to 649
ohms
1200
32 to
0 to
0.000 mV 4.933 mV
3416
1880
4 to 20 mA
4.00 mA
0 to 20 mA
0.00 mA
0 to 10 mV
0.00 mV
0 to 50 mV
0.00 mV
0 to 100 mV
0.00 mV
1 to   5 Volts
1.00 Volts
0 to   5 Volts
0.00 Volts
0 to 10 Volts
0.00 Volts
0 to 1250 mV
0.00 mV
-30 to 510 mV
-30.00
mV
100%
ohms
1646.445
ohms
20.00 mA
20.00 mA
10.00 mV
50.00 mV
100.00 mV
5.00 Volts
5.00 Volts
10.00 Volts
1250.00
mV
510.00 mV
99