Selections or
Function
Range of
Prompt
Setting
FM version
Input 1 Filter
0 to 120
seconds No
filter = 0
Input 1
Burnout
Upscale
Burnout
Downscale
Burnout
Parameter Definition
Filter for Input 1 —A software digital filter is
provided for Input 1 to smooth the input signal.
You can configure the first order lag time constant
from 1 to 120 seconds. If you do not want filtering,
enter 0.
Burnout Protection (Sensor Break)
input types with upscale or downscale protection if
the input fails.
It will force the Input 1 signal to the full scale value
when the sensor fails. Diagnostic message IN1
FAIL intermittently flashed on the lower display.
It will force the Input 1 signal to the lower range
value when the sensor fails. Diagnostic message
IN1 FAIL intermittently flashed on the lower
display.