Chapter 3 -  Installation
Items
Dimensions
Wiring
Connections
Power
Consumption
Power Inrush
Current
Weight
Isolation
(Functional)
Surge Withstand
Capability (SWC)
29
Specifications
Communication Status (Bluetooth, Ethernet, and Modbus)
See
Overall Dimensions
Screw terminals on the rear of the case.
See  Wiring Diagrams for more information.
20 VA maximum (90 to 264 Vac)
15 VA maximum (24 Vac/dc)
10A maximum for 4 ms (under operating conditions),
reducing to a maximum of 225 mA (90 to 264 Vac operation)
or 750 mA (24 Vac/dc operation) after one second.
CAUTION:  When applying power to more than one
instrument, make sure that sufficient power is supplied.
Otherwise, the instruments may not start up normally
due to voltage drop from the inrush current.
3 lbs. (1.3 kg)
AC Power(100~240VAC)
inputs and outputs to withstand a HIPOT potential of 3000
Vac for 60 seconds, from earth ground to withstand a HIPOT
potential of 1500 Vac for 60 seconds per EN61010-1 and CSA
Std C22.2 No.24-15.
DC Power(24VDC/AC)
and outputs and earth ground to withstand a HIPOT potential
of 840 Vac for 60 seconds per EN61010-1 and CSA Std C22.2
No.24-15.
Analog Inputs and Outputs
isolated from all other circuits to withstand a HIPOT potential
of 1500 Vac for 60 seconds.
: With a working voltage of 125/250 Vac, these
Relay Contacts
are electrically isolated from all other circuits to withstand a
HIPOT potential of 3000 Vac for 60 seconds per EN61010-1
and CSA Std C22.2 No.24-15.
Immunity: ANSI/IEEE C37.90.1, Surge Withstand Capability
(SWC) (Formerly IEEE 472). Mains power input and relay
contact outputs: 2.5 kV, Common Mode, and Differential
for more information.
: Electrically isolated from all other
: Electrically isolated from all other inputs
,
Digital Inputs and Outputs
: Electrically