Step
Action
2
Set LOCK in the Tuning Set Up group to NONE.
3
Tag and disconnect the field wiring, at the rear of the controller,
from terminals 12 (+) and 13 (–). See Wiring Connections for
Calibrating Auxiliary Output.
4
Connect a milliammeter across these terminals.
Figure 7-1: Wiring Connections for Calibrating Auxiliary Output
Procedure
The procedure for calibrating the auxiliary output is listed in the
following table
Make sure Lockout in the security group set to "NONE" See Security
Set Up Group for more information.
Chapter 7 - Output Calibration
112