Chapter 12 - Standard Modbus Read, Write and Override Parameters
Parameter Description
Alarm #2 SP #1
Alarm #2 SP #2
Alarm #2 Action
SP Low Limit
SP High Limit
Working Set Point
PV Override Value
SP Override Value
213
Register Address
Hex
Decimal
0017
40024
0018
40025
0019
40026
001A
40027
001B
40028
001C
40029
0020
40033
0021
40034
Access
Description
prescale *1
Bit 0: 1 = Alarm 1 SP 1
State is High, or Event is
End; 0 = State is Low, or
Event is Begin
Bit 1: 1 = Alarm 1 SP 2
State is High, or Event is
End; 0 = State is Low, or
Event is Begin
R/W
Signed 16 bit integer,
prescale * 10
R/W
Signed 16 bit integer,
prescale * 10
R
Signed 16 bit integer,
prescale *1
Bit 0: 1 = Alarm 2 SP 1
State is High, or Event is
End; 0 = State is Low, or
Event is Begin
Bit 1: 1 = Alarm 2 SP 2
State is High, or Event is
End; 0 = State is Low, or
Event is Begin 
R/W
Signed 16 bit integer,
prescale * 10 ( Note 1)
R/W
Signed 16 bit integer,
prescale * 10 ( Note 1)
R/W
Signed 16 bit integer,
prescale * 10 ( Note 1)
R/W
Signed 16 bit integer,
prescale * 10
R/W
Signed 16 bit integer,
prescale * 10 ( Note 1)

Advertisement