Chapter 7 -  Output Calibration
Table 7-2: Auxiliary Output Calibration Procedure
Step
Operation
1
Enter
Calibration
Mode
2
Calibrate 0 %
3
Calibrate 100
%
4
Exit the
Calibration
Mode
113
Press
Result
Setup key
Enter into the Setup mode.
Setup key or
Until you see Auxiliary Calib.
Increment
key or
Decrement
key
Function
Enter into the first function prompt Zero Value
key
of the Auxiliary Calib set up group. Press the
Function key again to enter the configuration
prompt of Zero Value.
Until the desired 0 % output is read on the
Increment
milliammeter. Normally, this will be the setting
key or
that produces 4 mA.
Decrement
key
If tuning Zero Value of 0-20 mA output type,
the output should be tuned to non-zero value
first, and then tuned back to the edge. The
edge means that the output will be greater
than 0 mA when the Increment key is pressed,
and the output will still be 0 mA when the
Decrement key is pressed.
Function
To store the 0 % value.
key
Increment
Until you see Span Value.
key or
Decrement
key
Function
Enter into the configuration prompt of Span
key
Value.
Until the desired 100 % output is read on the
Increment
milliammeter. Normally, this will be the setting
key or
that produces 20 mA.
Decrement
key
Function
The controller stores the span value.
key
Lower
To exit the calibration mode.