Function
Selection or Range
Prompt
of Setting
Lower Display
Upper Display
A2S1 Type
A2S1 Value
Value in
engineering units
A2S1 State
HIGH Alarm
LOW Alarm
A2S1
0.0 to 100.0 % of
Hysteresis
span or full output
as appropriate
A2S2 Type
Value in
engineering units
Parameter
Definition
100 % away from the alarm setpoint.
Configure the hysteresis of the alarms based
on INPUT signals as a % of input range span.
Configure the hysteresis of the alarm based on
OUTPUT signals as a % of the full scale output
range.
ALARM 2 SETPOINT 1 TYPE—Select what you
want Setpoint 1 of Alarm 2 to represent.
The selections are the same as A1S1 Type.
ATTENTION: Not applicable with Relay
Duplex unless using Dual Relay PWA.
ALARM 2 SETPOINT 1 VALUE—This is the
value at which you want the alarm type chosen
in prompt A2S1 Type to actuate.
The details are the same as A1S1 VAL.
ALARM 2 SETPOINT 1 STATE—Same as
A1S1HL.
ALARM HYSTERESIS—A single adjustable
hysteresis is provided on alarms such that
when the alarm is OFF it activates at exactly
the alarm setpoint; when the alarm is ON, it
will not deactivate until the variable is 0.0 % to
100 % away from the alarm setpoint.
Configure the hysteresis of the alarms based
on INPUT signals as a % of input range span.
Configure the hysteresis of the alarm based on
OUTPUT signals as a % of the full scale output
range.
ALARM 2 SETPOINT 2 TYPE—Select what you
want Setpoint 2 of Alarm 2 to represent.
Chapter 4 - Configuration
76