Setting Up the Analog
Output Scale (cont.)
Procedure Options
Programming Site Data
5. At BASE, enter a flow rate value for the low end of the analog
output range by using the arrow keys. Press [
the cursor to desired location and press
or decrease the number and press [ENTER].
6. At FULL, enter a flow rate value for the high end of the analog
output range by using the arrow keys. Press [
the cursor to desired location and press
or decrease the number and press [ENTER].
7. At Error handling, press [ ] to select the desired option for
handling errors (HOLD, LOW, HIGH, or OTHER) and press [ENTER].
8. If OTHER is selected, the Forced milliamps display appears. This
allows the user to impose a set value for this option. Enter the
desired forced milliamps by using the arrow keys. Press [
[ ] to move the cursor to desired location and press
[ ]
to increase or decrease the number and press [ENTER].
After completing the above steps, the user program returns to the
Global I/O window. Do one of the following:
To continue regular programming, refer to Appendix A, Menu
Maps, to navigate to the desired menu.
To leave the user program, press [ESC] four times.
September 2004
]
and [ ] to move
[ ] and [ ]
to increase
]
and [ ] to move
[ ]
[ ]
and
to increase
]
and
[ ] and
2-29