8.2

FDAP Technical Specification

Model Numbers
Multiple Standards/Field Protocols ISA100 Wireless and WirelessHART
Weight
Dimensions
Power
External Ports and Connections
Internal Connections
Environmental Ratings
Operating Temperature
Transportation and Storage
Temperature
Operating Humidity
Transportation and Storage
Humidity
Mechanical Shock
Data Rates and Modulations
Frequency Band and Operating
Channels
FDAP1 (Class 1 Div 1/Zone 0)
FDAP2 (Class 1 Div 2/Zone 2)
3.86 kg (5.5 lbs)
216 x 170 x 86 mm (8.47 x 6.73 x 3.37 in)
24 VDC +/- 10% at 2 Watts
90 – 264 VAC, 50/60 Hz
2 X external antenna ports for 2.4 GHz ISA100 Wireless field instruments
1 X 10/100 Mbps auto negotiation Ethernet port
1 X shielded power cable
1 X grounding cable
IP66, G3 Corrosion resistance per ANSI/ISA-S71.04-1985,
NEMA Type 4X (FM only)
FDAP1: -40 to +70 °C
FDAP2: -40 to +60 °C
-40 to +85 °C
0~100% non-condensing
0~100% non-condensing
4G
Radio: 250 Kbps, DSSS/ O-QPSK
Wire: 10/100 Mbps Fast Ethernet
Unlicensed ISM Band (2.4 – 2.483 GHz)
15 DSSS channels for ISA100 Wireless
6 FDAP MAINTENANCE AND TROUBLESHOOTING