3 FDAP INSTALLATION
3.7

Ground the FDAP Gen3

The FDAP Gen3 provides internal and external grounding point to meet various local and regulatory grounding
requirements. You should ensure that the FDAP Gen3 are grounded properly by a certified and authorized
personnel, and that it conforms to all applicable codes and regulations. The materials required to provide a
proper ground are defined by local regulations and should be obtained locally to ensure that the correct safety
environment is achieved.
Attention
1.
2.
3.8

Ground the FDAP1/FDAP2

The FDAP1/FDAP2 provides internal and external grounding point to meet various local and regulatory
grounding requirements. You should ensure that the FDAP1/FDAP2 are grounded properly by a certified and
authorized personnel, and that it conforms to all applicable codes and regulations. The materials required to
provide a proper ground are defined by local regulations and should be obtained locally to ensure that the
correct safety environment is achieved.
Attention
1.
2.
24
www.honeywell.com
The recommended AWG of the ground cable from FDAP Gen3 ground to the ground pit should be at least 12
or better.
Ground Pit should be maintained as per the NEC recommendation. The ground resistance should be less than 5
ohms so that it provides safety to FDAP Gen3 under environmental transients such as lightning, sandstorm, etc.
The recommended AWG of the ground cable from FDAP1/FDAP2 ground to the ground pit should be at least
12 or better.
Ground Pit should be maintained as per the NEC recommendation. The ground resistance should be less than 5
ohms so that it provides safety to FDAP1/FDAP2 under environmental transients such as lightning,
sandstorm, etc.