3. Strip the outer jacket of the CAT5e cable and connect the shield drain wire to the internal
grounding lug on the conduit hub. Do not strip the individual twisted pair wires.
4. Connect the twisted pair wires to the IDC following the color chart marked next to the IDC.
Note that the color chart on the
conforms to EIA/TIA 568B color code which is the predominant color code for CAT5e cable.
Refer to "Table 3: Ethernet IDC block pin-out" for the necessary adjustment if the older
EIA/TIA 568B color coded cable is used. Most of the CAT5E cables conform to TIA/EIA 568B.
PIN #
1
2
3
4
5
6
PIN #
TIA/EIA 568A
7
8
Testing Ethernet connection
A standard RJ-45 modular jack is available on the
used to test cable integrity after terminating the cable at the IDC connector. After terminating the field cable at
the IDC, connect the cable tester to the RJ-45 jack. An end-to-end cable test can then be performed to ensure
proper wiring at the IDC connector.
FDAP1/FDAP2
Table 3: Ethernet IDC block pin-out
TIA/EIA 568A
TIA/EIA 568B
FDAP1/FDAP2
Power and I/O board assumes that the cable
TIA/EIA 568B
Data
Unused
Unused
Power and IO board. The RJ-45 jack may be
3 FDAP INSTALLATION
Data
Transmit+
Transmit-
Receive+
Unused
Unused
Receive-
35