6 FDAP MAINTENANCE AND TROUBLESHOOTING
Quality of Service
Transmit Power (Maximum)
Receive Sensitivity (Typical)
Network Interface
Number of Supported ISA100
Wireless and WirelessHART
Field Instruments
Number of Supported Enraf
FlexLine Radar Gauges /
Wireless Field Interface (WFI)
Maximum Number of Wireless
Network Hops Between an
Access Point and a Field Device
Warranty
ECCN
www.honeywell.com
Supported
18 dBm
-100 dBm @ 250 kbps
10/100 Mbps Ethernet, auto-sensing
10 ISA100 Wireless or 8 WirelessHART Field Instruments at 0.5 second reporting
rate OR
5 ISA100 Wireless and 4 WirelessHART Field Instruments at 0.5 second reporting
rate
25 ISA100 Wireless or 25 WirelessHART Field Instruments at 1 second reporting
rate OR
12 ISA100 Wireless and 12 WirelessHART Field Instruments at 1 second reporting
rate
50 ISA100 Wireless or 50 WirelessHART Field Instruments at 2 seconds reporting
rate OR
25 ISA100 Wireless and 25 WirelessHART Field Instruments at 2 seconds
reporting rate80 ISA100 Wireless Field Instruments at 5 seconds or 80
WirelessHART Field Instruments at 4 seconds reporting rate OR
40 ISA100 Wireless and 40 WirelessHART Field Instruments at 5 seconds and 4
seconds reporting rate respectively
100 ISA100 Wireless Field Instruments at 10 seconds or slower or100
WirelessHART Field Instruments at 8 seconds or slower reporting rate OR
50 ISA100 Wireless and 50 WirelessHART Field Instruments at 10 seconds and 8
seconds or slower reporting rate respectively
13 Enraf FlexLine Radar Gauges / WFI
4 Hops
1 Year
5A002 ENC