Cisco ONS 15454 M6 Installation Manual page 37

Hide thumbs Also See for ONS 15454 M6:
Table of Contents

Advertisement

Installing the ONS 15454 M6 Shelf
DLP-G564 Mounting the Bracket with Air Deflectors (Front-to-Back) on the ONS 15454 M6 Shelf for ETSI Rack Configuration
• 100G-LC-C, 10x10G-LC, or CFP-LC
• EDRA1-26, EDRA1-35, EDRA2-26, or EDRA2-35
Use the standard brackets directly to mount the ONS 15454 M6 shelf.
Step 5
Align the screw holes on the left front air deflector with the screw holes on the left side of the chassis.
Step 6
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 7
Return to your originating procedure (NTP).
DLP-G564 Mounting the Bracket with Air Deflectors (Front-to-Back) on the
ONS 15454 M6 Shelf for ETSI Rack Configuration
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Caution
Use only the fastening hardware provided with the ONS 15454 M6 to prevent loosening, deterioration, and
electromechanical corrosion of the hardware and joined material.
Procedure
Step 1
Place the right front air deflector flush against the right side of the chassis (see Diagram 1 of
Mounting the Air Deflectors (Front-to-Back) on the ONS 15454 M6 Shelf for ETSI Rack Configuration, on
page
Step 2
Align the screw holes on the right front air deflector with the screw holes on the right side of the chassis.
Step 3
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 4
Place the left back air deflector flush against the chassis as shown in Diagram 2 of
Air Deflectors (Front-to-Back) on the ONS 15454 M6 Shelf for ETSI Rack Configuration, on page
This task installs the bracket with air deflectors (front-to-back) on the ONS 15454
M6 shelf for ETSI rack configuration.
Note
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
NTP-G305 Unpack and Inspect the ONS 15454, ONS 15454 M2, and ONS 15454
M6 Shelves
As needed
Onsite
None
38).
The air deflectors can be installed only in the front position of the
chassis.
Installing the ONS 15454 M6 Shelf
Figure 35:
Figure 35: Mounting the
38.
37