Backup Battery: 6V, 3.1AH, Honeywell part number K14139, (included)
Expected Battery Life: 5 Years (approx.)
Fault Relay Output: Open collector, 12VDC, .25W max.
Positive Trigger Level: 6V or greater = positive trigger. (4V or less = restore.)
Negative Trigger Level: 4V or less = negative trigger. (6V or greater = restore.)
RF
Transceiver Type: Quad-Band GSM/GPRS Class 10
Modulation: GMSK
Antenna: Internal GSM quad-band antenna 1.3 dBi gain
Transmission
Frequency
Band
(MHz)
GSM 850
824-849
GSM 900
890-915
GSM 1800
1710-1785
GSM 1900
1850-1910

Ethernet

Network Standard: IEEE 802.3u compliant
Data Rate: 10Base-T / 100Base-T with auto detect
Ethernet Cable: Cat. 5 (min), MDI/MDI-X auto crossover

Environmental

Operating temperature: -20ºC to +55ºC, for UL/ULC installations 0ºC to +49ºC
Storage temperature: -40º to +70ºC
Humidity: 0 to 95% relative humidity, non-condensing
Altitude: to 10,000 ft. operating, to 40,000 ft. storage

Compatibility

For a list of control panels that are compatible with various features of this device, go to:
http://www.security.honeywell.com/hsc/resources/MyWebTech.
After logging on, select the applicable communication product, and then select "Compatibility
Chart" under Essential Docs.
For UL and ULC Fire and Burglary installations, compatible control panels are:
 Vista-32FB
 Vista-128FBP
 Vista-250FBP
For UL and ULC Fire and Burglary installations, compatible receivers are:
MX8000 (UL – can be used for secondary reporting in ECP mode and Zone Trigeer mode.
Shall be used for opening and closing ring back with the control panel dialer)
7810iR-ENT (UL – must be the primary alarm receiver.)
 Ademco 685
Transmit
Power
Frequency
(dBm)
33
33
30
1805-1880
30
1930-1990
for UL installations 0% to 85%; for ULC installations 0% to 93%
Receive
Receive
Sensitivity
(MHz)
(dBm)
869-894
-107
935-960
-107
-106
-105.5
 FA1670C
 FA1700C
Section 1: General Information
Number
Channel
of
Spacing
Channels
(MHz)
124
200
124
200
374
200
299
200
Duplex
Separation
(kHz)
45
45
95
80