Honeywell AlarmNet IGSMV Installation And Setup Manual page 35

Internet communication module
Table of Contents

Advertisement

PROMPTS
GSM Flt Time
23
(60 mins)_
Notify Panel Of_
24
(Neither Fault)_
Flt Rel ON Y/N
25
(N)_
26
Pwr Loss Rpt
Y/N (Y)_
27
Low Bat Rpt Y/N
(Y)_
Tamper Rpt Y/N
28
(Y)_
29
Lynx Panic Y/N
(N)_
4204/
ZONE
ENTRY
TRIG.
2-4204
Section 3: Programming the IGSMV
OPTIONS
[01-99]
In the event the module detects a communica-
tion path failure, enter the time delay (in
minutes) before the IGSMV notifies the central
station. A GSM failure will always be sent to
the central station as Secondary
Communication Path Failure.
UL/ULC: Must be one (01) minute.
If "Both IP and GSM Fault" is selected, the
[Neither
device will only notify the control panel if both
fault]
communication paths fail, but will always send
notification of either failure to the central
[Both IP
station. NOTE: The fault relay output (if
and GSM
programmed) will be triggered only if "Both IP
Faults]
and GSM Faults" is selected.
Press the [space] key to scroll through choices.
UL/ULC: Must be set to "Both IP and GSM
Faults".
If enabled, the fault open collector output is
[Y], [N]
normally energized to ground, and de-energizes
(open circuit) in the event of a module fault.
For conditions that trip the fault relay refer to
Module Supervision Features in Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring for Module Fault Relay in Section 2.
UL/ULC: Must be set to "Y".
Sends a primary power loss report to the central
[Y], [N]
station within 1-3 hours after its detection. A
restore report is sent within 1-3 hours after
power is restored.
UL/ULC Standard Installations (using
transformer and battery): Must be set to "Y".
ULC Commercial Fire & Burglary
Installations (powered from the control panel):
Must be set to "N."
[Y], [N]
Sends a low-battery report when a low battery
condition exists. A low-battery restore is
automatically sent when the low battery
condition clears.
UL/ULC Standard Installations (using
transformer and battery): Must be set to "Y".
ULC Commercial Fire & Burglary
Installations (powered from the control panel):
Must be set to "N."
[Y], [N]
Sends a tamper report when the module detects
a tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.
UL/ULC: Must be set to "Y".
[Y], [N]
Applies only if used with a Lynx, LynxR or
LynxR-EN control LRR trigger connected to the
module's zone terminal.
Reports a Panic alarm on zone 3 when the
module detects a single pulse on zone 1.
No restores are generated for a Panic alarm.
UL/ULC: The LYNX controls have not been
DESCRIPTION
3-15

Advertisement

Table of Contents
loading