Wiring For Module Fault Relay; Ethernet Connections - Honeywell AlarmNet IGSMV Installation And Setup Manual

Internet communication module
Table of Contents

Advertisement

Wiring for Module Fault Relay

You may wire and program the module's fault output trigger for fail-safe mode (see the
question "FLT REL ON Y/N").
To sense a module fault at the control panel, make connections as shown in Figure 2-6,
including the proper EOL resistor required by the control..
UL / ULC
Figure 2-6. Wiring the IGSMV Fault Relay to a Control Panel Zone for Normally Closed Fault

Ethernet Connections

 For UL installations, the Cat. 5 Ethernet connection between the IGSMV and the router
U L
Connect one end of the Ethernet cable (Category 5) to the IGSMV's RJ45 Ethernet connector
and the other end to the cable/DSL router as shown in the figure below.
For Commercial Burglary, a 24 hour zone (supervisory) must be assigned on the
control panel, with the communication module's fault relay wired to that zone.
12V AUX
GND
ZONE IN (+)
RESISTOR
CONTROL PANEL
cannot exceed 12 feet with both the IGSMV and the router located within the same room.
Use a Listed cable/DSL router suited for the application.
7720P
PROGRAM
CONNECTOR
J1
BATTERY
CONNECTOR
Figure 2-7. Ethernet Connections
TRANSFORMER
TB1
AC INPUT 1
1
AC INPUT 2
2
ECP (+) VOLTAGE INPUT
3
GND
4
2K EOL
11
RAD FLT
COMMUNICATIONS
MODULE
TO ROUTER
Section 2: Mounting and Wiring
BATTERY
J1
RJ45
(FOR INTERNET
CONNECTION)
2-7