Section 3: Programming the IGSMV
OPTIONS
Press the [space] key to toggle between the
 Present
options. Press [ENTER] to select the
 Auto Detect
configuration.
If "Present" is chosen, it is assumed that an
IP is connected to the device. If it is not
detected, a Primary Comm Path Failure
message will be delivered after the
programmed fault time expires.
If "Auto Detect" is chosen, the device will
always try to use IP to communicate but it
will not generate a Primary Comm Path
Failure unless it previously detected the
presence of IP. As soon as the presence of IP
is detected, a Primary Comm Path Restore
message is generated and the value of IP
Connectivity programming parameter is
changed from "Auto Detect" to "Detected".
From this point on, the software expects
connectivity. The auto detect logic will
resume only when the parameter is changed
back to "Auto Detect".
[Y] = review
Reviewing Programming Mode Entries
To review the programming options (to
[N] = exit
ensure that the correct entries have been
made), press [Y]. The programming
questions are displayed again. Use the
up/down arrow keys to scroll through the
program fields without changing any of the
values. If a value requires change, simply
type in the correct value. When the last field
is displayed, the "REVIEW?" question again
appears.
To exit the programming mode, press [N]
in response to the "REVIEW?" question, and
refer to Exiting Programming Mode below.