Backup Battery Connection; Initial Power-Up Sequence - Honeywell AlarmNet IGSMV Installation And Setup Manual

Internet communication module
Table of Contents

Advertisement

Shared
Transformer
Installation
NOTE:
When calculating the total load on the auxiliary power output of the control panel, budget 10mA
for the IGSMV when using ECP mode.

Backup Battery Connection

The included battery (K14139) is used for backup in the event of power loss to the
communications module. It does not provide power to the control panel.
In ULC installations this battery is not connected, and all backup power is supplied by the
control panel.
The battery can provide over 24 hours of system life in the event of a power failure.
 A programmable power loss message can alert the AlarmNet Control Center when system
power is lost (power loss messages are reported within 1-3 hours of actual loss).
 The module transmits a low-battery message (programmable) when the battery reaches
5.7V ±5%, indicating subsequent messages may not be transmitted.
 The system shuts down when the battery falls below 5.1V, and radio transmissions are no
longer possible.
 If system power is restored before the module shuts down, a power restore message is sent
within 1-3 hours after power is restored, and the battery is recharged using the IGSMV's
built-in battery charger. If system power is restored after the IGSMV has shut down, a
power-on reset condition exists, the module initializes itself and the battery will recharge.
Install the battery as follows, and refer to the Summary of Connections diagram at the end of
this document.
1. Place the battery inside the case back.
2. Snap the right side of the battery clip onto the inside of the case back and secure the left
side with the screw provided.
Do not plug the battery in until after you have powered-up the IGSMV.

Initial Power-Up Sequence

Before connecting power, check that the following have been completed:
 If using ECP, 4204 or 2-4204 Mode, terminal block TB1 V+ and GND terminals are
connected to the control panel's auxiliary power output: 12VDC nominal.
 Plug in the transformer. Then connect the red and black battery cables to the battery
terminals. Connect battery cable to connector J1.
 Power up the control panel. (Initially, all IGSMV programming options are set to the
factory default settings.)
COMMUNICATIONS
CONTROL PANEL
MODULE
1
2
30 FT. MAX TO MODULE
18 AWG. WIRE (MIN)
Figure 2-8. Powering the IGSMV
1 2
1361
TRANSFORMER
Section 2: Mounting and Wiring
TO 110 VAC
UNSWITCHED
OUTLET
2-9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alarmnet igsmvcn

Table of Contents