EK280

5.4 Information input inactive

Each of inputs 2 to 6 (terminals DE2 to DE6) can be programmed as inactive information inputs. This means:
When the input "+" and "-" are open (not electrically connected), the message "13" is entered in the
momentary status of the relevant input.
The status message can then be used, for example to create an archive entry or to switch an output.
To program an input as an active warning input, send the relevant parameter files from the following to the
EK280 using the parameterization program "enSuite" (see chapter 3.6
Input 2 = Message signal not activ.wpp
Input 3 = Message signal not activ.wpp
Input 4 = Message signal not activ.wpp
Input 5 = Message signal not activ.wpp
Input 6 = Message signal not activ.wpp

5.5 Time-synchronous input

Any of the inputs 2 to 6 (terminals DE2 to DE6) can be used as a time-synchronous input. This means:
When the input poles are electrically connected, the clock is set to the full hour. However the following
conditions must be met:
The input pulse must occur within one minute to or past a full hour. Whichever is the time on the
EK280.
There can be only one synchronization per hour.
To program an input as a time synchronous input, send the relevant parameter files from the following to the
EK280 using the parameterization program "enSuite" (see chapter 3.6
Input 2 = Time sync..wpp
Input 2 = Time sync..wpp
Input 2 = Time sync..wpp
Input 2 = Time sync..wpp
Input 2 = Time sync..wpp
It is recommended, to seal one input for time synchronization, to prevent misuse.
Application Manual
"Send parameter
file", page 10):
"Send parameter
file", page 10):