Before Installation - Honeywell IdentIPoint Installation Instructions Manual

Intelligent smartcard system
Hide thumbs Also See for IdentIPoint:
Table of Contents

Advertisement

HONEYWELL IDENTIPOINT™ INTELLIGENT SMARTCARD SYSTEM
NOTE: For detailed connection diagrams see topics
Detailed Wiring Diagrams and Wiring Other
Devices.
NOTE: Any currently available IdentIPoint reader can be
used as an enrollment reader.
OVERVIEW
IdentIPoint is Honeywell's next generation smart card based
access control system in conjunction with Honeywell's award
winning Enterprise Buildings Integrator - EBITM. IdentIPoint
readers come with a powerful built-in controller thus
eliminating the need to install a separate multi-door access
controller. IdentIPoint offers flexible architecture options
including the option of connected and standalone readers.
The readers communicate with EBI over a wired or wireless*
Ethernet network.
The IdentIPoint hardware family consists of the following
models:
• Indoor / Outdoor basic readers - IP65 (BTBAS)
• Indoor readers with LCD & Keypad (BTSTD)
• Indoor readers with LCD, Keypad and Fingerprint
(BTFPT)2
• Remote Input Output Module (IOM) (BTIO)
IdentIPoint readers support the following Contactless Smart
Card Reader technologies:
• MIFARE Classic 1K, 4K
• MIFARE DESFire 4K
• MIFARE DESFire EV1 4K, 8K
IdentIPoint readers also support the following network
technologies:
• Wireless LAN IEEE802.11b/g standard; provides WPA
security for infrastructure mode of operation*.
• High speed 10/100 Mbps Ethernet connection for Wired
LAN via RJ45.
IdentIPoint readers support the following types of peripheral
connections:
• One RS485 serial bus (115200 baud) for IOM
• Bus Termination and BIAS for RS485 on board (jumpers or
dip switch)
• Digital Output 1 (current sinking at 1A, 24VDC max.)
• Supervised Inputs 3; capable of distinguishing 4 states
• Relay Contact 1 (1A-24VDC) - Form C
• Two Tamper Inputs:
— Inner Tamper Switch: Micro-switch (detecting casing
opening)
— Outer Tamper Switch: Optical (detecting unit dis-
mounted from wall)
95-7767
The readers work with 12V to 24VDC power supply or Power-
over-Ethernet (PoE)* conforming to the IEEE 802.3af
standard. All software and firmware is remotely upgradeable
over the network via EBI.
All the IdentIPoint readers are designed to work with an
optional remote IOM. The IOM is used when the control inputs
and outputs of the door are desired to be on the secure side of
the door - for high security installations. The IOM integrates
seamlessly with the readers via a secure encrypted RS485
bus. Up to four IOMs can be connected via the same bus to a
reader. The IOMs are independently addressable via DIP
switches.
The IOM supports the following types of Inputs and Outputs:
• Relay: 2 - (1A 24VDC) Form C
• Digital Input: 2
• Digital Output: 2 (current sinking; (max 24V 1A)
• Supervised Analog Inputs : 4 ; capable of distinguishing 4
states
• Supervised Analog Output 1 - repeats the last Supervisory
Input, SAI3
The IOM works with a 12V to 24VDC power supply. It is
possible to control one door using two Readers in IN & OUT
mode with the help of an IOM.
* See Table.1.
Models and Part Numbers
The IdentIPoint product-line consists of the following three
reader models and one input/output unit:
1. Basic: Basic Indoor / Outdoor reader with IP65 rating
(Part no.: BTBAS)
2. Standard: Indoor reader with LCD & Keypad (Part no.:
BTSTD)
3. Fingerprint: Indoor reader with LCD, Keypad and Fin-
gerprint unit (Part no.: BTFPT)
4. IOM: Remote Input Output Module (Part no.: BTIO)
NOTE:
1.
For device ratings, see product datasheet (Docu-
ment no. 74-5086).
2.
The BTFPT module is not UL294 listed and shall
not be used for UL applications.
3.
IP65 enclosure rating was not evaluated by UL.

BEFORE INSTALLATION

1. Verify the mounting locations with the job drawings.
2. Unpack the IdentIPoint reader, IOM and accessories
and check them. Report any damaged or missing com-
ponents to a Honeywell representative. A claim must be
filed with the commercial carrier responsible.
2