Power Wiring

IMPORTANT
Use a shielded power cable with a three-pin (or as
per local regulations) plug to draw mains power for
the power supply assembly. (The shielded wire is
required to meet FCC RF radiation limits.)
To route the power wiring
1. Using proper conduits, route the input power cable from
the mains supply to the input block of the power supply.
2. Route the +ve and -ve pairs of wires from the output
block of the power supply out of the power supply enclo-
sure via proper conduits.
Connection
Wire Gauge
Power Source to
18 AWG
Device (Reader
(0.8mm
or IOM)
AWG (1.7mm
Reader/IOM to
18 AWG
Digital Inputs
(0.8mm
Reader/IOM to
18 AWG
Digital Output or
(0.8mm
Lock
AWG (1.7mm
Reader to IOM
18 AWG
(Power)
(0.8mm
AWG (1.7mm
Reader to IOM
18 AWG
(RS485 comm.)
(0.8mm
Reader to IOM
18 AWG
(other than Power
(0.8mm
and RS485
comm.)
IOM to IOM
18 AWG
(RS485 comm.)
(0.8mm
Ethernet
CAT5
EACH DOOR STRIKE REQUIRES A 14507020-001 DIODE
SUPPRESSION NETWORK. DOOR STRIKE MAY DRAW A
MAXIMUM CURRENT OF 2A; REGULATED 12/ 24 VDC.
DOOR STRIKE AND REX MUST BE UL LISTED. SEE
FIG.25 THROUGH FIG.28 FOR TYPICAL DIODE SUP-
PRESSION NETWORK WIRING.
HONEYWELL IDENTIPOINT™ INTELLIGENT SMARTCARD SYSTEM
Table 2. Wire Sizes and Distances
Maximum Distance
See reader/IOM power requirements
2
(section Power Supply Recommendations
) to 15
of Assembly, Mounting and Installation
2
)
topic) and compensate for drop in voltage.
100m
2
)
100m subject to adequate power reaching
2
the output device or lock
) to 15
2
)
See IOM power requirements (section
2
Power Supply Recommendations of
) to 15
Assembly, Mounting and Installation topic)
2
)
and compensate for drop in voltage.
500m
2
)
100m
2
)
500m
2
)
100m
3. Connect the +ve and -ve of wires to IdentIPoint devices.
For readers, connect the +ve to the red and the -ve to
the black wires of the 9-pin Molex terminal respectively.
(See Fig.6 for details on Molex terminal wire colors.)

Tamper Protection

IMPORTANT
IdentIPoint readers are equipped with tamper protec-
tion features. They must be permanently mounted
before commissioning. Attempting to open a reader
case without putting it in maintenance mode will dis-
able the reader, and require recommissioning. For
details on how to deal with a tampered reader please
refer the EBI documentation set.
DOOR CONTACTS MUST BE UL LISTED. MAXIMUM WIRE
LENGTH 500 FT (152 M). WIRE TYPE 18 AWG (0.8 SQ
MM), 50 OHM 60 mA MAXIMUM. DOOR CONTACTS ARE
ONLY INTENDED FOR MONITORING DOOR POSITION.
THEY ARE NOT INTENDED FOR CONNECTION TO A
BURGLAR ALARM PANEL
EXIT SWITCH: WIRING MUST BE COMPLETED WITHIN
THE PROTECTED AREA OR NOT READILY ACCESSIBLE
OUTSIDE THE PROTECTED AREA. THE EXIT SWITCH
MUST BE UL LISTED.
23
Minimum
number of
conductors
Shielding
3
Unshielded
cable
recommended
2 per i/p
Optional
2 per o/p
Required for
power cable
connected to
output device or
lock
2
Required
3
Recommended
2 per connection
Optional
type
3
Recommended
Standard as in
Recommended
CAT5
95-7767