Honeywell IdentIPoint Installation Instructions Manual page 36

Intelligent smartcard system
Hide thumbs Also See for IdentIPoint:
Table of Contents

Advertisement

HONEYWELL IDENTIPOINT™ INTELLIGENT SMARTCARD SYSTEM
SAI-n
SAI-n GND
NOTE: REX and Door Sense support only Normally
Closed and not Normally Open positions, i.e.,
REX is detected when SAI switch is open, Door is
sensed as open when SAI switch is open.
CONNECTOR AND SWITCH
DESCRIPTIONS
For Readers:
Table 5. Reader J9 connector signals
Connector: J9
Pin
Number
Signal
1
Power-IN
2
Power-GND
3
Relay-Common
4
Relay-Normal
Close
5
Relay-Normal
Open
6
Supervisory Analog
Input (SAI) 0
7
SAI 0 GND
8
Supervisory Analog
Input (SAI) 1
9
SAI 1 GND
95-7767
Fig. 29. Connections for Supervisory Analog Inputs
Connector Wire
RED
BLACK
ORANGE
WHITE/
ORANGE
WHITE
GREEN
WHITE/GREEN
BLUE
WHITE/BLUE
36
1K Ω
Table 6. Reader J10 connector signals
Connector: J10
Pin
Number
Signal
1
Power Output for
Door Strike
2
Ground for Door
Strike
3
RS485-A
4
RS485-B
5
RS485-GND
6
Digital Output
(Current Sink)
7
Digital Output GND
8
Supervisory Analog
Input (SAI) 2
9
SAI2 GND
10
Frame GND (ESD
GND)
Table 7. Reader S1 DIP Switch settings
Position
Effect when "ON" (position left)
1
RS485-A pull up
2
RS485 termination
3
RS485-B pull down
4
Wi-fi Disable
Sensor
Switch
Connector Wire
RED
BLACK
YELLOW
WHITE/
YELLOW
GREY
ORANGE
WHITE/
ORANGE
VIOLET
WHITE/VIOLET
WHITE/BLACK

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents