Honeywell IdentIPoint Installation Instructions Manual page 27

Intelligent smartcard system
Hide thumbs Also See for IdentIPoint:
Table of Contents

Advertisement

NOTE: REX and Door Sense support only Normally
Closed and not Normally Open positions, i.e.,
REX is detected when SAI switch is open, Door is
sensed as open when SAI switch is open.
Single Reader with REX and IOM
To REX Switch
To Door Sensor
Separate Power Supply
can also be used for IOM.
To electrical
earth.
If unavailable,
connect to
Power-GND.
Fig. 22. Connections for single reader with REX and IOM (S1 DIP switch settings shown)
HONEYWELL IDENTIPOINT™ INTELLIGENT SMARTCARD SYSTEM
To LAN
J9
Relay-NO
Relay-NC
Relay-C
DC – Power
Power-GND
12 to 24V
Power-IN
If PoE is not used
To electrical
earth
earth.
If unavailable,
connect to
Power-GND.
DI-0
GND
GND
DO-0
DI-1
GND
GND
DO-1
1KΩ
SAI-0
GND
2KΩ
GND
ILK-0
1KΩ
SAI-1
GND
2KΩ
GND
ILK-1
SAI-2
SAI 2
485-
485
GND
GND
485-B
SAI-3
485-A
GND
N.C
SAO
N.O
GND
GND
RL0 C
RL0-C
12V
N.C
GND
N.O
FGND
RL1-C
IO Module
Ethernet
PIN
PIN
J10
9
1
Power-OUT
SAI-1-GND
8
2
Power-GND
SAI-1
SAI-0-GND
7
3
RS485-A
6
4
RS485-B
SAI-0
5
5
RS485-GND
4
6
DO
3
7
DOGnd
2
SAI-2
8
1
SAI-2-GND
9
Frame-GND
10
IdentIPoint Reader
LEGEND
Power – Min. 18 AWG
Power Gnd – Min. 18 AWG
Ethernet – CAT5
Signal/Power – Min. 18 AWG
Signal – Min. 18 AWG
Signal – Min. 18 AWG
Comm. – Min. 18 AWG
Comm. – Min. 18 AWG
Comm. – Min. 18 AWG
To Door Lock
S1
27
S1
95-7767