Fig. 30. S1 DIP Switch settings on reader and IOMs for RS485 termination
IOM Address Set up
Each IOM should have its own address. S3 DIP switch on the
IOM holds the RS485 address of each unit. The addresses
can range from 1 to 127, with position 1 corresponding to
20=1, position 2 to 21=2 and so on as shown in Fig.31. Never
use zero as IOM address as zero is reserved for the master
device.
SUM all ON bit values
Never use address zero
Fig. 31. IOM Address set up
95-7767
IOM (Slave 1)
IOM (Slave 1)
IOM (Slave 1)
IOM (Slave 1)
Termination OFF
Termination OFF
Termination OFF
Termination OFF
Termination OFF
Termination OFF
Termination OFF
Termination OFF
To work out the address, select a combination of bit locations
on the DIP switch. Each bit has its own value representation.
The RS485 address is obtained by adding all ON-bit values.
E.g. Decimal value 37 will be obtained by turning ON bits 1, 3
and 6 which is equivalent to 1+4+32.
NOTE: It is recommended not to attach more than 4 IOM
+
1
+
2
+
4
+
8
+
1
6
+
3
2
+
6
4
40
IOM (Slave 2)
IOM (Slave 2)
IOM (Slave 2)
IOM (Slave 2)
Termination ON
Termination ON
Termination ON
Termination ON
Termination ON
Termination ON
Termination ON
Termination ON
units to the RS485 bus to maintain a reasonable
signal/response time delay between the reader
and the IOMs. Hence IOM addresses must be
from 1 to 4 only. See Fig.32 for S3 DIP switch set-
tings for up to 4 IOMs.