Copy Mode - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

78 Control panels

Copy mode

The Basic control panel can store a full set of drive parameters and up to two user
sets of drive parameters to the control panel. Uploading and downloading can be
performed in local control. The control panel memory is non-volatile.
In the Copy mode, you can do the following:
• Copy all parameters from the drive to the control panel (uL – Upload). This
includes all defined user sets of parameters and internal (not adjustable by the
user) parameters.
• Restore the full parameter set from the control panel to the drive (dL A –
Download all). This writes all parameters, including the internal non-user-
adjustable motor parameters, to the drive. It does not include the user sets of
parameters.
Note: Only use this function to restore a drive, or to transfer parameters to
systems that are identical to the original system.
• Copy a partial parameter set from the control panel to a drive (dL P – Download
partial). The partial set does not include user sets, internal motor parameters,
parameters 9905...9909, 1605, 1607, 5201, nor any group
parameters.
The source and target drives and their motor sizes do not need to be the same.
• Copy user set 1 parameters from the control panel to the drive (dL u1 – Download
user set 1). A user set includes group
internal motor parameters.
The function is only shown on the menu when User set 1 has been first saved
using parameter
and then uploaded to panel.
• Copy user set 2 parameters from the control panel to the drive (dL u2 – Download
user set 2). As dL u1 – Download User set 1 above.
• Start, stop, change the direction and switch between local and remote control.
www.aotewell.com
9902 APPLIC MACRO
sales@aotewell.com
99 START-UP DATA
(see section
user macros
Industry Automation
53 EFB PROTOCOL
parameters and the
on page 112)
+86-755-8660-6182

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents