Check the direction of the motor rotation.
• If the drive is in remote control (REM shown on
the left), switch to local control by pressing
• To go to the Main menu, press
bottom line shows OUTPUT; otherwise press
bottom.
• Press keys
press
• Increase the frequency reference from zero to
a small value with key
• Press
• Check that the actual direction of the motor is
the same as indicated on the display (FWD
means forward and REV reverse).
• Press
To change the direction of the motor rotation:
• If parameter
visible, first set parameter
VIEW
• Invert the phases by changing the value of
parameter
to 1 (YES), or vice versa.
• Verify your work by applying input power and
repeating the check as described above. Set
parameter
Check that the drive state is OK.
Basic control panel: Check that there are no
faults or alarms shown on the display. If you want
to check the LEDs on the front of the drive, switch
first to remote control (otherwise a fault is
generated) before removing the panel and
verifying that the red LED is not lit and the green
LED is lit but not blinking.
Assistant control panel: Check that there are no
faults or alarms shown on the display and that the
panel LED is green and does not blink.
HongKong|UK|China
www.aotewell.com
DIRECTION OF THE MOTOR ROTATION
repeatedly until you see MENU at the
/
until you see "rEF" and
.
to start the motor.
to stop the motor.
9914 PHASE INVERSION
to 3
(LONG
VIEW).
9914
to the opposite, ie from 0 (NO)
1611
back to 2
The drive is now ready for use.
sales@aotewell.com
Start-up and control with I/O 61
.
LOC
REM
if the
.
is not
1611 PARAMETER
(SHORT
VIEW).
FINAL CHECK
Industry Automation
xxx
LOC
.
SET
forward
reverse
direction
direction
1611
LOC
PAR
9914
LOC
PAR
+86-755-8660-6182
Hz
FWD
FWD
FWD