Motor potentiometer macro

This macro provides a cost-effective interface for PLCs that vary the speed (output
frequency) of the motor using only digital signals. To enable the macro, set the value
of parameter
9902 APPLIC MACRO
For the parameter default values, see section
page 165. If you use other than the default connections presented below, see section
I/O terminals
on page 49.

Default I/O connections

max. 500 ohm
1)
If DI3 and DI4 are both active or inactive, the
output frequency reference is unchanged.
The existing output frequency reference is
stored during stop and power down.
www.aotewell.com
to 4
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Not in use by default. 0...10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Not in use by default. 0...10 V
6
GND
Analog input circuit common
7
AO
Output frequency value: 0...20 mA
8
GND
Analog output circuit common
2)
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1)
13 DI2
Forward (0) / Reverse (1)
14 DI3
Output frequency reference up
15 DI4
Output frequency reference down
16 DI5
Constant speed 1: parameter
X1B
17 ROCOM
18 RONC
19 RONO
20 DOSRC
21 DOOUT
22 DOGND
sales@aotewell.com
(MOTOR
POT).
Default values with different macros
Relay output 1
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]
2)
360 degree grounding under a clamp.
Tightening torque: 0.4 N·m (3.5 lbf·in).