298 Fieldbus control with the embedded fieldbus

Modbus mapping

The following Modbus function codes are supported by the drive.
Function
Code
Hex (dec)
Read Coil
01 (01)
Status
Read Discrete
02 (02)
Input Status
Read Multiple
03 (03)
Holding
Registers
Read Multiple
04 (04)
Input
Registers
Force Single
05 (05)
Coil
Write Single
06 (06)
Holding
Register
Diagnostics
08 (08)
Force Multiple
0F (15)
Coils
Write Multiple
10 (16)
Holding
Registers
Read/Write
17 (23)
Multiple
Holding
Registers
www.aotewell.com
Additional information
Reads discrete output status. The individual bits of the control word
are mapped to coils 1...16. Relay outputs are mapped sequentially
beginning with Coil 33 (eg, RO1 = Coil 33).
Reads discrete input status. The individual bits of the status word
are mapped to inputs 1...16 or 1...32, depending on the active
profile. Terminal inputs are mapped sequentially beginning with
input 33 (eg, DI1 = Input 33).
Reads the contents of registers in a slave device.
Parameter sets, control, status and reference values are mapped
as holding registers.
Reads multiple input registers. The 2 analog input channels are
mapped as input registers 1 and 2.
Writes a single discrete output. The individual bits of the control
word are mapped to Coils 1...16. Relay outputs are mapped
sequentially beginning with Coil 33 (eg, RO1 = Coil 33).
Writes to a single register in a slave device.
Parameter sets, control, status and reference values are mapped
as holding registers.
Provides a series of tests for checking the communication between
the master and the slave devices, or for checking various internal
error conditions within the slave.
The following subcodes are supported:
00 Return Query Data: The data passed in the request data field is
to be returned in the response. The entire response message
should be identical to the request.
01 Restart Communications Option: The slave device serial line
port must be initialized and restarted, and all of its communication
event counters cleared. If the port is currently in Listen Only Mode,
no response is returned. If the port is not currently in Listen Only
Mode, a normal response is returned before the restart.
04 Force Listen Only Mode: Forces the addressed slave device to
Listen Only Mode. This isolates it from the other devices on the
network, allowing them to continue communicating without
interruption from the addressed remote device. No response is
returned. The only function that is processed after this mode is
entered is the Restart Communications Option function (subcode
01).
Writes multiple discrete outputs. The individual bits of the control
word are mapped to Coils 1...16. Relay outputs are mapped
sequentially beginning with Coil 33 (eg, RO1 = Coil 33).
Writes to the registers (1 to approximately 120 registers) in a slave
device.
Parameter sets, control, status and reference values are mapped
as holding registers.
Performs a combination of one read operation and one write
operation (function codes 03 and 10) in a single Modbus
transaction. The write operation is performed before the read
operation.