Reference Select - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

All parameters
No.
Name/Value
REVERSE
REQUEST
1011 PANEL FORCE
STOP
DISABLE
ENABLE
11 REFERENCE
SELECT
1101 KEYPAD REF
SEL
REF1(Hz/rpm)
REF2(%)
1102 EXT1/EXT2
SEL
EXT1
DI1
DI2
DI3
DI4
DI5
EXT2
COMM
TIMED FUNC 1 Timed EXT1/EXT2 control selection. Timed function 1 active
TIMED FUNC 2 See selection
TIMED FUNC 3 See selection
TIMED FUNC 4 See selection
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
www.aotewell.com
Description
Fixed to reverse
Control of rotation direction allowed
Enables stopping the drive from the control panel even
when not in local control.
Control panel stop button is active only in local control
Drive can be stopped from the control panel in remote
control
Panel reference type, external control location selection and
external reference sources and limits
Selects the type of the reference in the local control mode.
Frequency reference in Hz
%-reference
Defines the source from which the drive reads the signal
that selects between the two external control locations,
EXT1 or EXT2.
EXT1 active. The control signal sources are defined by
parameters
1001 EXT1 COMMANDS
SELECT.
Digital input DI1. 0 = EXT1, 1 = EXT2.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
EXT2 active. The control signal sources are defined by
parameters
1002 EXT2 COMMANDS
SELECT.
Fieldbus interface as the source for EXT1/EXT2 selection,
ie Control word
0301 FB CMD WORD 1
drives profile
5319 EFB PAR 19
sent by the fieldbus controller through the embedded
fieldbus (Modbus) to the drive. For the Control word bits,
see sections
DCU communication profile
ABB drives communication profile
= EXT2, timed function 1 inactive = EXT1. See parameter
group
36 TIMED
FUNCTIONS.
TIMED FUNC
TIMED FUNC
TIMED FUNC
Inverted digital input DI1. 1 = EXT1, 0 = EXT2.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
sales@aotewell.com
Actual signals and parameters 179
and
1103 REF1
and
1106 REF2
bit 5 (with ABB
bit 11). The Control word is
on page
on page 302.
1.
1.
1.
Industry Automation
Def/FbEq
2
3
DISABLE
0
1
REF1(Hz/
rpm)
1
2
EXT1
0
1
2
3
4
5
7
8
307
and
9
10
11
12
-1
-2
-3
-4
-5