Embedded Fieldbus Faults; No Master Device; Same Device Address; Incorrect Wiring - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

Embedded fieldbus faults

Embedded fieldbus faults can be traced by monitoring group
parameters. See also fault/alarm

No master device

If there is no master device on line, parameter
EFB CRC ERRORS
What to do:
• Check that the network master is connected and properly configured.
• Check the cable connection.

Same device address

If two or more devices have the same address, parameter
value increases with every read/write command.
What to do:
• Check the device addresses. No two devices on line may have the same address.

Incorrect wiring

If the communication wires are swapped (terminal A on one device is connected to
terminal B on another device), parameter
unchanged and parameter
What to do:
• Check the EIA-485/RS-232 interface connection.
www.aotewell.com
SERIAL 1
values remain unchanged.
5307 EFB CRC ERRORS
sales@aotewell.com
ERR.
5306 EFB OK MESSAGES
5307 EFB CRC ERRORS
5306 EFB OK
MESSAGESS value remains
increases.
Industry Automation
Fault tracing 327
53 EFB PROTOCOL
and
5307
+86-755-8660-6182

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents