ABB ACS310 User Manual page 205

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

All parameters
No.
Name/Value
2202 ACCELER
TIME 1
0.0...1800.0 s
2203 DECELER
TIME 1
0.0...1800.0 s
www.aotewell.com
Description
Defines the acceleration time 1, that is, the time required for
the speed to change from zero to the speed defined by
parameter
2008 MAXIMUM
• If the speed reference increases faster than the set
acceleration rate, the motor speed follows the
acceleration rate.
• If the speed reference increases slower than the set
acceleration rate, the motor speed follows the reference
signal.
• If the acceleration time is set too short, the drive
automatically prolongs the acceleration in order not to
exceed the drive operating limits.
Actual acceleration time depends on parameter
SHAPE 1
setting.
Time
Defines the deceleration time 1, that is, the time required for
the speed to change from the value defined by parameter
2008 MAXIMUM FREQ
• If the speed reference decreases slower than the set
deceleration rate, the motor speed follows the reference
signal.
• If the reference changes faster than the set deceleration
rate, the motor speed follows the deceleration rate.
• If the deceleration time is set too short, the drive
automatically prolongs the deceleration in order not to
exceed drive operating limits.
If a short deceleration time is needed for a high inertia
application, note that the ACS310 cannot be equipped with
a brake resistor.
Actual deceleration time depends on parameter
RAMP SHAPE 1
setting.
Time
sales@aotewell.com
Actual signals and parameters 205
FREQ.
to zero.
Industry Automation
Def/FbEq
5.0 s
2204 RAMP
1 = 0.1 s
5.0 s
2204
1 = 0.1 s
+86-755-8660-6182

Hide quick links:

Advertisement

Table of Contents
loading