276 Actual signals and parameters
All parameters
No.
Name/Value
DI1
www.aotewell.com
Description
Enables the Interlock function and assigns a digital input
(starting with DI1) to the interlock signal for each PFC relay.
These assignments are defined in the following table and
depend on:
• the number of PFC relays (number of parameters
1401...1403
and
1410
• the Autochange function status (disabled if
AUTOCHNG INTERV
No. of
Autochange disabled
PFC
(Parameter 8118)
relays
0
DI1: Speed reg motor
DI2...DI5: Free
1
DI1: Speed reg motor
DI2: First PFC relay
DI3...DI5: Free
2
DI1: Speed reg motor
DI2: First PFC relay
DI3: Second PFC relay
DI4...DI5: Free
3
DI1: Speed reg motor
DI2: First PFC relay
DI3: Second PFC relay
DI4: Third PFC relay
DI5...DI5: Free
4
DI1: Speed reg motor
DI2: First PFC relay
DI3: Second PFC relay
DI4: Third PFC relay
DI5: Fourth PFC relay
5
Not allowed
sales@aotewell.com
with value = 31 [PFC])
= 0.0, and otherwise enabled).
Autochange enabled
(Parameter 8118)
Not allowed
DI1: First PFC relay
DI2...DI5: Free
DI1: First PFC relay
DI2: Second PFC relay
DI3...DI5: Free
DI1: First PFC relay
DI2: Second PFC relay
DI3: Third PFC relay
DI4...DI5: Free
DI1: First PFC relay
DI2: Second PFC relay
DI3: Third PFC relay
DI4: Fourth PFC relay
DI5: Free
DI1: First PFC relay
DI2: Second PFC relay
DI3: Third PFC relay
DI4: Fourth PFC relay
DI5: Fifth PFC relay
Industry Automation
Def/FbEq
1
8118