2.5

Advanced Diagnostic

This screen provides information regarding Advanced diagnostics. Including Tracking,
Error Log, Configuration History and a Review tab.

2.5.1. Tracking:

Refer below tables Advanced Diagnostic details.
Comm Module
Diagnostics – Advanced Diagnostics – Modules – Comm Module
Key: Plain = Read only Bold = Configurable Bold underline = Method Bold italic = Table or graph
Comm Stress Life
Comm Service
Life
Power Cycles
Power Up
Diagnostics
Power Cycle
TimeStamp
Maximum ET
Limit
Maximum ET
Value
ET Tracking
ET Up Cnt
Page 76
Percent of Communication Module service life spent in stressful
conditions. Indicates the % of service life where one or more of
processor core temperature, or electronics temperature are within
10% of respective range limits.
Percent of the expected Service Life that the Communications
Module has been in service. Value is based on electronics
temperature. Service life accumulates faster at higher temperatures
with an exponential relationship.
The total number of times the device has been reset by power cycle
Displays time since last power cycle (in minutes)
Communications board Electronics Temperature (ET) highest
operating limit from specification.
Communications board Electronics Temperature (ET) highest
measured value
The total number of minutes that the Communications board
Electronics Temperature (ET) has exceeded the upper stress limit
(ET Upper Limit)
SMV800 Modbus User's Guide