Figure 2-2: Rtd Range Configuration; Figure 2-3: Current Range Settings - Honeywell SMV800 User Manual

Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

Background
You can set the LRV and URV for PT by either typing in the desired values on the MODBUS-
RTU host Process Temperature Config tab or applying the corresponding LRV and URV input
signals directly to the transmitter. The LRV and URV set the desired zero and span points for your
measurement range as shown the example in
The URV changes automatically to compensate for any changes in the LRV and maintain
the present span (URV – LRV). See
If you must change both the LRV and URV, always change the LRV first. However, if the
change in the LRV would cause the URV to exceed the URL, you would have to change
the URV to narrow the span before you could change the LRV
Damping
Adjust the damping time constant for Process Temperature to reduce the output noise. Default
value of damping is 0.5 seconds. Damping can be configured from 0 to 102 seconds.
Page 34
Figure
2-2.

Figure 2-2: RTD Range Configuration

Figure 2-3

Figure 2-3: Current Range Settings

SMV800 Modbus User's Guide
for an example.
Revision 1.0