Honeywell SMV800 User Manual page 135

Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

Warning
119
Information
120
Revision 1.0
No_Flow_Outpu
t
Bit - 6
Simulation
Mode
Bit - 6
Bit 7-15
Unused
adc_reference_f
ault
Bit - 0
temp_unreliable
_comm
Bit -1
ts_no_factory_c
Bit - 2
alibration
SMV800 Modbus User's Guide
The Flow Algorithm has
been configured for "No
Flow Output".
Process variables
simulation enabled
NA
The reference voltage
measurement in
one of the two Analog to
Digital Converter
(ADC) parts in the
Temperature module is
not operating correctly. The
process temperature
measurement may be
affected.
If there is no proper
communication between
Communication Board and
Temperature Sensor Board
(Terminal) or invalid data
on communication line due
to noise
Temperature sensor
module factory calibration
is missing
This bit will be set when
flow output algorithm type
configured as No flow
output. Configure Flow
Output algorithm type if
required otherwise ignore
this warning.
This bit is set when any of
the process variables like
DP, SP, PT and Flow are
configured for Simulation.
Simulation mode(sim) is
enabled for the Diff, Static
Press, Process Temp or
Flow. Sim mode simplifies
testing of flow calc prior to
online operation.\nWhile
conducting testing, the
status indicates that sim is
being used. When testing
is completed, clear the sim
mode for the inputs to
return to true process
measurement
NA
Reset the device. If the
problem persists,
replace the Temperature
module.
User can verify the
cable/connector between
communication and
Temperature sensor board
(Terminal Board) to ensure
that it is not damaged.
Check for bent pins.If
cable/connector is not the
problem, replace the
Communication module.If
problem still persists,
replace the Terminal
board.
Return the device for
Factory Calibration
Page 123