Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

Simulated
300
Flow
Options
302
Present
Reserve For
304
Device
Specific
Reserve For
306
Device
Specific
Reserve For
313
Device
Specific
Selected
315
calibration set
for DP
Available
316
calibration set
for DP
Selected
317
calibration set
for SP
Available
318
calibration set
for SP
Req Calib Sel
319
DP
Req Calib Sel
320
SP
Sensor
321
firmware
revision
Meterbody Bar
325
Code
adc Filter
331
selection
Page 152
Simulated Flow value when
Simulation setting is ON
Pay for play option. This
parameter gives information
that what are options present
in transmitter.
NA
NA
NA
The currently selected
custom factory calibration
(A,B, C) for Differential
Pressure
The available custom factory
calibration (A,B, C) for
Diffrential Pressure
The currently selected
custom factory calibration
(A,B, C) for Static Pressure
The available custom factory
calibration (A,B, C) for Static
Pressure
Allows selection of one of the
available custom factory
calibrations for Differential
Pressure
Allows selection of one of the
available custom factory
calibrations for Static
Pressure
Sensor Firmware Version
Bar Code number of Meter
Body
Configuration option for
Standard or Fast Speed of
Response
SMV800 Modbus User's Guide
RO
float
RO
uint32
Bit 0 = Reserved
Bit 1:-> 0 = Universal
Input Option not present ;1
= Universal Input option
present
Bit 2:-> 0 = Flow Output
Option not present ;1 =
Flow Output Option
present
Bit 3 to 15 = Reserved
RO
uint8
0 = CAL A
1 = CAL B
2 = CAL C
3 = Best Fit
RO
uint8
0 = CAL A
1 = CAL B
2 = CAL C
3= Best Fit
RO
uint8
0 = CAL A
1 = CAL B
2 = CAL C
3 = Best Fit
RO
uint8
0 = CAL A
1 = CAL B
2 = CAL C
3= Best Fit
R/W
uint8
0 = CAL A
1 = CAL B
2 = CAL C
3 = Best Fit
R/W
uint8
0 = CAL A
1 = CAL B
2 = CAL C
3 = Best Fit
RO
string
RO
string
R/W
uint8
0 = Std SOR
1 = Fast SOR
N/A
N/A
N/A
Revision 1.0