Honeywell SMV800 User Manual page 203

Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

NA
Temp Suspect
Input
Sensor Char
CRC Failure
Sensor NVM
Details of
Corrupt
Critical
Fault
Sensor RAM
Failure
Sensor Code
Corrupt
Sensor Flow
Failure
Revision 1.0
NA
The fault is set for
the following
conditions.
• If the measured CJ
value is below -50
degC or above 90
degC
• If the internal ADC
Temperature module
is reporting
corruption in the
temperature
Characterization data
Temperature module
is reporting
corruption
of the Non-Volatile
Memory data (NVM)
Temperature module
is reporting
corruption in the
Random Access
Memory (RAM)
Temperature module
is reporting
corruption in
sensor firmware
Temperature module
firmware Program
Flow Failure. This
fault will get set if any
of the critical part of
the code is not
executed after
expected duration.
SMV800 Modbus User's Guide
NA
Bit - 9
Bit - 10
Power cycle the
device. If the problem
persists, replace the
Bit - 11
Terminal Board.
Power cycle the
device and if fault is
cleared ensure to
configure sensor
Bit - 12
parameters. If the
problem persists,
replace the Terminal
Board.
Power cycle the
device. If the problem
persists, replace the
Bit - 13
Terminal Board.
Power cycle the
device. If the problem
Bit - 14
persists, replace the
Terminal Board.
Power cycle the
device. If the problem
persists, replace the
Terminal Board.
Bit - 15
116