Honeywell SMV800 User Manual page 206

Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

Comm Sec NC
Failure
Sensing Sec NC
Warning
Failure
CJ Out Of Limit
No Factory
Calibration
Page 194
This is a roll-up
Power cycle the
status bit that is set
device and if problem
when any of the
persists replace
communication
communication
module non critical
module
status is set such as
• Display NVM
Corrupt
This is a roll-up
Refer detailed status
status bit that is set
bits corresponding to
when any of the
pressure module in
pressure and
register 121 and
temperature sensing
temperature module
modules non critical
in register 120.
status is set such as
• Unreliable
Communication
• Sensor Input Out
Of Range
• CJ Out Of Limit
• Excess Calibration
Correction
• CJ CT Delta
Warning
The Internal Cold
Junction
Verify that the
Temperature
environmental temp is
(CJ) measured in the
within spec. If it is,
Temperature
Temperature module
module is outside of
may have been
the specified range.
damaged. Replace
Range limits are -40
the Temperature
to 85 degrees C.
module
This is roll up status
Refer status bits
bit set for the
corresponding to
following:
factory calibration
• Temperature
status of pressure in
sensor module
register 121 and
factory calibration
temperature module
missing
in register 120.
• Pressure sensor
Accordinly return the
module factory
module for factory
calibration missing
calibration.
Factory Calibration
for either
Temperature
module or Pressure
module is missing.
Accuracy is
compromised if not
calibrated.
SMV800 Modbus User's Guide
Bit - 0
Bit -1
118
Bit - 2
Bit - 3
Revision 1.0