Honeywell SMV800 User Manual page 151

Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

Database
122
Fault
Information 1
Database
123
Fault
Information 2
Reserve
124
Revision 1.0
Database Fault Information 1
Database Fault Information 2
Reserve Address
SMV800 Modbus User's Guide
RO
uint8
Bit - 0 NVM copy of
Common database block
found corrupt.
Bit - 1 NVM copy of Vital
Configuration database
block found corrupt.
Bit - 2 NVM copy of
General Configuration
database block found
corrupt.
Bit - 3 NVM copy of
Configuration Change
database block found
corrupt.
Bit - 4 NVM copy of
Advanced Configuration
database block found
corrupt.
Bit - 5 NVM copy of
Display View/Screens
Configuration database
block found corrupt.
Bit - 6 NVM copy of
Display Common
Configuration
database block found
corrupt.
Bit - 7 NVM copy of
Totalizer Configuration
database block found
corrupt.
RO
uint8
Bit - 0 NVM copy of
Miscellaneous
Configuration database
block found corrupt.
Bit -1 NVM copy of
totalizer value block is
found corrupt
Bit - 2 NVM copy of
totalizer value block is
found corrupt
Bit - 3 NVM copy of
advance flow value block
is found corrupt
Bit - 4 NVM copy of
totalizer value back up
block is found corrupt
Bit - 5 NVM copy of user
variables block is found
corrupt
NA
NA
Page 139