B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 29 of 61)
ADDR
REGISTER NAME
6391
Bank overvoltage 1 phase B operate voltage
6392
Bank overvoltage 1 phase C operate voltage
6393
...Repeated for bank phase overvoltage 2
6396
...Repeated for bank phase overvoltage 3
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 modules)
63C0
Negative Sequence Instantaneous OC 1 Function
63C1
Negative Sequence Instantaneous OC 1 Signal Source
63C2
Negative Sequence Instantaneous Overcurrent 1 Pickup
63C3
Negative Sequence Instantaneous Overcurrent 1 Delay
63C4
Negative Sequence Instantaneous OC 1 Reset Delay
B
63C5
Negative Sequence Instantaneous Overcurrent 1 Block
63C7
Negative Sequence Instantaneous Overcurrent 1 Target
63C8
Negative Sequence Instantaneous Overcurrent 1 Events
63C9
Reserved (8 items)
63D1
...Repeated for Negative Sequence Instantaneous OC 2
Negative Sequence Overvoltage (Read/Write Grouped Setting)
6440
Negative Sequence Overvoltage Function
6441
Negative Sequence Overvoltage Source
64A42
Negative Sequence Overvoltage Pickup
6443
Negative Sequence Overvoltage Pickup Delay
6444
Negative Sequence Overvoltage Reset Delay
6445
Negative Sequence Overvoltage Block
6447
Negative Sequence Overvoltage Target
6448
Negative Sequence Overvoltage Events
6449
...Repeated for module number 2
6452
...Repeated for module number 3
Time of day timer settings (read/write, grouped, 5 modules)
6570
Time of day timer 1 function
6571
Time of day timer 1 start time
6573
Time of day timer 1 stop time
6575
Time of day timer 1 targets
6576
Time of day timer 1 events
6577
...Repeated for time of day timer 2
657E
...Repeated for time of day timer 3
6585
...Repeated for time of day timer 4
658C
...Repeated for time of day timer 5
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000
Phase Undervoltage 1 Function
7001
Phase Undervoltage 1 Signal Source
7002
Phase Undervoltage 1 Pickup
7003
Phase Undervoltage 1 Curve
7004
Phase Undervoltage 1 Delay
7005
Phase Undervoltage 1 Minimum Voltage
7006
Phase Undervoltage 1 Block
7008
Phase Undervoltage 1 Target
7009
Phase Undervoltage 1 Events
700A
Phase Undervoltage 1 Measurement Mode
700A
Reserved (6 items)
7013
...Repeated for Phase Undervoltage 2
7015
...Repeated for Phase Undervoltage 2
7017
...Repeated for Phase Undervoltage 2
701B
...Repeated for Phase Undervoltage 2
701C
...Repeated for Phase Undervoltage 2
B-36
0 to 65.535
0 to 65.535
0 to 4294967295
0 to 4294967295
0 to 2359
0 to 2359
0 to 4294967295
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
pu
0.001
pu
0.001
0 to 1
---
1
0 to 5
---
1
0 to 30
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0 to 1.25
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
---
1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0 to 3
pu
0.001
0 to 1
---
1
0 to 600
s
0.01
0 to 3
pu
0.001
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
APPENDIX B
FORMAT
DEFAULT
F001
0
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F001
1000
F001
0
F001
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F001
300
F001
50
F001
50
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F050
0
F001
2359
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F167
0 (SRC 1)
F001
1000
F111
0 (Definite Time)
F001
100
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F186
0 (Phase to
Ground)
F001
0