Advertisement

5 SETTINGS
e) NEGATIVE-SEQUENCE OVERVOLTAGE(ANSI 59Q, IEC PTOV)

PATH: SETTINGS
GROUPED ELEMENTS
 NEG SEQ OV1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
There is one negative-sequence overvoltage element available per CT bank, to a maximum of three.
The negative-sequence overvoltage element may be used to detect loss of one or two phases of the source, a reversed
phase sequence of voltage, or a non-symmetrical system voltage condition.
Figure 5–79: NEGATIVE-SEQUENCE OVERVOLTAGE SCHEME LOGIC
GE Multilin
SETTING GROUP 1(6)
NEG SEQ OV1
FUNCTION: Disabled
NEG SEQ OV1 SIGNAL
SOURCE: SRC 1
NEG SEQ OV1 PICKUP:
0.300 pu
NEG SEQ OV1 PICKUP
DELAY:
0.50 s
NEG SEQ OV1 RESET
DELAY:
0.50 s
NEG SEQ OV1 BLOCK:
Off
NEG SEQ OV1 TARGET:
Self-reset
NEG SEQ OV1 EVENTS:
Disabled
C70 Capacitor Bank Protection and Control System
5.6 GROUPED ELEMENTS


VOLTAGE ELEMENTS
NEG SEQ OV1(3)
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 1.250 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5
5-181