5.6 GROUPED ELEMENTS
f) PHASE CURRENT UNBALANCE (ANSI 60P, IEC PVCB/PTOC)

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE CURRENT
 UNBALANCE 1
5
5-154
SETTING GROUP 1(6)
CUR UNBALCE 1
FUNCTION: Disabled
CUR UNBALCE 1 DIF
MESSAGE
SOURCE: SRC 1
CUR UNBALCE 1 BANK
MESSAGE
SOURCE: SRC 1
CUR UNBALCE 1 INHNT
MESSAGE
FACTOR A: 0.0000
CUR UNBALCE 1 INHNT
MESSAGE
FACTOR B: 0.0000
CUR UNBALCE 1 INHNT
MESSAGE
FACTOR C: 0.0000
CUR UNBALCE 1 STG 1A
MESSAGE
PICKUP: 0.020 pu
CUR UNBALCE 1 STG 2A
MESSAGE
PICKUP: 0.030 pu
CUR UNBALCE 1 STG 3A
MESSAGE
PICKUP: 0.040 pu
CUR UNBALCE 1 STG 4A
MESSAGE
PICKUP: 0.050 pu
CUR UNBALCE 1 STG 1B
MESSAGE
PICKUP: 0.020 pu
CUR UNBALCE 1 STG 2B
MESSAGE
PICKUP: 0.030 pu
CUR UNBALCE 1 STG 3B
MESSAGE
PICKUP: 0.040 pu
CUR UNBALCE 1 STG 4B
MESSAGE
PICKUP: 0.050 pu
CUR UNBALCE 1 STG 1C
MESSAGE
PICKUP: 0.020 pu
CUR UNBALCE 1 STG 2C
MESSAGE
PICKUP: 0.030 pu
CUR UNBALCE 1 STG 3C
MESSAGE
PICKUP: 0.040 pu
CUR UNBALCE 1 STG 4C
MESSAGE
PICKUP: 0.050 pu
CUR UNBALCE 1 STG 1
MESSAGE
PKP DELAY: 30.00 s
CUR UNBALCE 1 STG 2
MESSAGE
PKP DELAY: 10.00 s
CUR UNBALCE 1 STG 3
MESSAGE
PKP DELAY:
C70 Capacitor Bank Protection and Control System


PHASE CURRENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: –0.1000 to 0.1000 in steps of 0.0001
Range: –0.1000 to 0.1000 in steps of 0.0001
Range: –0.1000 to 0.1000 in steps of 0.0001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s