GE C70 Instruction Manual page 48

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

2.2 SPECIFICATIONS
NEUTRAL CURRENT UNBALANCE
Auto-setting:
Number of elements:
Inherent unbalance factor: magnitude of 0 to 0.1500 in steps of
Number of trip/alarm stages: 4, with individual timers per stage
Pickup threshold:
2
Pickup level accuracy:
Hysteresis:
Slope:
Pickup delay:
Timer accuracy:
Operate time:
NEUTRAL VOLTAGE UNBALANCE
Operation:
Auto-setting:
Number of elements:
Compensating factor:
Number of trip/alarm stages: 4 with individual timers
Pickup threshold:
Slope:
Pickup level accuracy:
Hysteresis:
Pickup delay:
Timer accuracy:
Operate time:
PHASE UNDERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Curve shapes:
Curve multiplier:
Curve timing accuracy
at <0.90 x pickup:
2-16
on demand from keypad
1 per CT bank, to a maximum of 3
0.0001, angle of 0 to 359° in steps of 1
0.001 to 5.000 pu of ground input CT in
steps of 0.001
0.002 pu for <1 pu current and < 20 CT
mismatch between phase and neutral
CT
3% or 0.001 pu, whichever is greater
0.0 to 10.0% in steps of 0.1
0 to 600.00 s in steps of 0.01
±3% of operate time or ±35 ms, which-
ever is greater
<35 ms at 60 Hz
compensated for inherent bank and sys-
tem unbalance
on demand from keypad
1 per VT bank, maximum of 3
0.7500 to 1.2500 in steps of 0.0001
0.001 to 1.000 pu of nominal of the bank
neutral point VT in steps of 0.001
0 to 10% in steps of 0.1
0.003 pu for <10 VT mismatch between
phase and neutral VT
3% or 0.001 pu whichever is greater
0 to 600.00 s in steps of 0.01
±3% of operate time or ±35 ms, which-
ever is greater
<35 ms at 60 Hz
0.000 to 3.000 pu in steps of 0.001
102 to 103% of pickup
±0.5% of reading from 10 to 208 V
GE IAV Inverse;
Definite Time (0.1s base curve)
Time dial = 0.00 to 600.00 in steps of
0.01
±3.5% of operate time or ±1/2 cycle
(whichever is greater) from pickup to
operate
C70 Capacitor Bank Protection and Control System
2 PRODUCT DESCRIPTION
BANK OVERVOLTAGE
Operation:
per phase, 3 stages of definite-time, 1
stage of inverse-time
Application:
grounded and ungrounded banks
Number of elements:
1 per VT bank, maximum of 3
Pickup threshold:
0.800 to 2.000 pu of bus voltage in steps
of 0.001, per phase
Pickup level accuracy:
0.002 pu for operating voltage <70 V
Hysteresis:
0.02 pu
Pickup delay:
0 to 600.00 s in steps of 0.01
Curve:
any user-programmable FlexCurve
Timer accuracy:
±3% of operate time or ±35 ms, which-
ever is greater
Operate time:
<35 ms at 60 Hz
PHASE OVERVOLTAGE
Voltage:
Phasor only
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0.00 to 600.00 in steps of 0.01 s
30 ms at 1.10  pickup at 60 Hz
Operate time:
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
NEUTRAL OVERVOLTAGE
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0.00 to 600.00 s in steps of 0.01 (definite
time) or user-defined curve
Reset delay:
0.00 to 600.00 s in steps of 0.01
Curve timing accuracy
at >1.1 x pickup:
±3.5% of operate time or ±1 cycle
(whichever is greater) from pickup to
operate
30 ms at 1.10  pickup at 60 Hz
Operate time:
AUXILIARY OVERVOLTAGE
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0 to 600.00 s in steps of 0.01
Reset delay:
0 to 600.00 s in steps of 0.01
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
30 ms at 1.10  pickup at 60 Hz
Operate time:
NEGATIVE SEQUENCE OVERVOLTAGE
Pickup level:
0.000 to 1.250 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0 to 600.00 s in steps of 0.01
Reset delay:
0 to 600.00 s in steps of 0.01
Timer accuracy:
±3% of operate time or ±20 ms, which-
ever is greater
<30 ms at 1.10  pickup at 60 Hz
Operate time:
GE Multilin