5.8 INPUTS AND OUTPUTS
DIRECT OUT 2 OPERAND:
DIRECT OUT 3 OPERAND:
DIRECT OUT 4 OPERAND:
Signal flow between the three IEDs is shown in the figure below:
UR IED 1
Figure 5–118: SIGNAL FLOW FOR DIRECT INPUT AND OUTPUT – EXAMPLE 3
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 should be ANDed in FlexLogic and the resulting operand configured as the permission to trip (
setting).
5

PATH: SETTINGS
INPUTS/OUTPUTS
 GOOSE ANALOG
 INPUT 1
The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series
devices. The following settings are available for each GOOSE analog input.
ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offline
and the
ANALOG 1 DEFAULT MODE
point number. Because of the large range of this setting, not all possible values can be stored. Some values may be
rounded to the closest possible floating point number.
ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is "Last Known", the value of the
GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is
"Default Value", then the value of the GOOSE analog input is defined by the
GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actual
values display of the corresponding GOOSE analog input value.
GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log values in other C70 features, such as FlexElements. The base factor is applied to the GOOSE analog input Flex-
Analog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
5-246
"
HYB POTT TX1
"
DIRECT INPUT 5
"
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 5
DIRECT INPUT 6


IEC 61850 GOOSE ANALOGS

ANALOG
1 DEFAULT:
1000.000
ANALOG
1 DEFAULT
MESSAGE
MODE: Default Value
GOOSE ANALOG
MESSAGE
UNITS:
GOOSE ANALOG
MESSAGE
is set to "Default Value".This setting is stored as an IEEE 754 / IEC 60559 floating
C70 Capacitor Bank Protection and Control System
"
" (forward a message from 1 to 3)
" (forward a message from 3 to 1)
UR IED 2
DIRECT INPUT 5
DIRECT OUT 2 = HYB POTT TX1
DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6
UR IED 3
DIRECT INPUT 5
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1

GOOSE ANALOG INPUT 1(32)
Range: –1000000.000 to 1000000.000 in steps of 0.001
Range: Default Value, Last Known
Range: up to 4 alphanumeric characters
1
Range: 0.000 to 1000000000.000 in steps of 0.001
1 PU:
1.000
ANALOG 1 DEFAULT
5 SETTINGS
842717A1.CDR
HYB POTT RX1
5.8.11 IEC 61850 GOOSE ANALOGS
setting.
GE Multilin