5 SETTINGS
g) BANK VOLTAGE DIFFERENTIAL (ANSI 87V, IEC PDIF)

PATH: SETTINGS
GROUPED ELEMENTS
 VOLTAGE
 DIFFERENTIAL 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
SETTING GROUP 1(6)
VOLTAGE DIF 1
FUNCTION: Disabled
VOLTAGE DIF 1 BUS
SOURCE: SRC 1
VOLTAGE DIF 1 TAP
SOURCE: SRC 1
VOLTAGE DIF 1 BANK
GROUND: Grounded
VOLTAGE DIF 1 MATCH
FACTOR A:
2.0000
VOLTAGE DIF 1 MATCH
FACTOR B:
2.0000
VOLTAGE DIF 1 MATCH
FACTOR C:
2.0000
VOLTAGE DIF 1 STG 1A
PICKUP: 0.010 pu
VOLTAGE DIF 1 STG 2A
PICKUP: 0.020 pu
VOLTAGE DIF 1 STG 3A
PICKUP: 0.030 pu
VOLTAGE DIF 1 STG 4A
PICKUP: 0.040 pu
VOLTAGE DIF 1 STG 1B
PICKUP: 0.010 pu
VOLTAGE DIF 1 STG 2B
PICKUP: 0.020 pu
VOLTAGE DIF 1 STG 3B
PICKUP: 0.030 pu
VOLTAGE DIF 1 STG 4B
PICKUP: 0.040 pu
VOLTAGE DIF 1 STG 1C
PICKUP: 0.010 pu
VOLTAGE DIF 1 STG 2C
PICKUP: 0.020 pu
VOLTAGE DIF 1 STG 3C
PICKUP: 0.030 pu
VOLTAGE DIF 1 STG 4C
PICKUP: 0.040 pu
VOLTAGE DIF 1 STG 1
PKP DELAY: 30.00 s
VOLTAGE DIF 1 STG 2
PKP DELAY: 10.00 s
C70 Capacitor Bank Protection and Control System
5.6 GROUPED ELEMENTS


VOLTAGE ELEMENTS
VOLTAGE DIFFERENTIAL 1(3)
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Grounded, Ungrounded
Range: 0.5000 to 2000.0000 in steps of 0.0001
Range: 0.5000 to 2000.0000 in steps of 0.0001
Range: 0.5000 to 2000.0000 in steps of 0.0001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01