Template 13: HP CO2 Single Detector
B.13 Template 13: HP CO2 Single Detector
OUTPUT CIRCUITS
#1 RELEASE CIRCUIT 1
#2 RELEASE CIRCUIT 2
#3 ALARM NAC
#4 RELEASE STAGE
DISCHARGE
Table Legend:
* = shows relationship only, will not activate a release circuit
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
"Release Stage/NAC Operation" on page 85).
Input Zone Types:
•
Zone 1 = circuit with type code of 2-wire heat
•
Zone 2 = circuit with type code of 2-wire heat
•
Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release
•
Zone 4 = circuit with type code of Discharge Pressure Switch
•
Zone 5 = circuit with type code of Supervisory
•
Zone 6 = circuit with type code of Supervisory
Output Circuit Types:
•
Output 1 = Release Circuit 1 - Supervised for shorts
•
Output 2 = Release Circuit 2 - Supervised for shorts
•
Output 3 = Alarm NAC - silenceable, programmed for Cross-Zone operation for Release
Circuit 1 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit 2:" on page 61)
•
Output 4 = Release Stage Discharge - silenceable, programmed Release Stage Discharge
operation for Release Circuit 1 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit
2:" on page 61)
Timers
•
Pre-Discharge Delay: Release 1 - set for 30 seconds; Release 2 - set for 30 seconds
•
Discharge: Release 1 - set for Always On; Release 2 - set for Always On
•
Waterflow Delay Timer - set for 90 seconds
•
AC Loss Delay Timer - set for 2 hours
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Template 13: HP CO2 Single Detector
1
2
2-WIRE
2-WIRE
MANUAL
HEAT
HEAT
RELEASE
X
X
X
X
X
X
Xr
Xr
INPUT ZONES
3
4
DISCHARGE
SUPERVISORY
PRESSURE
X
X*
X
X*
X
X
Xr
Xr
FACP Configuration Templates
5
6
SUPERVISORY
137