Honeywell MRP-2002 Instruction Manual page 133

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Template 11: Agent/Waterflow - Cross-Zone
Device Installation Example for Template 11
Output
Output
Circuit #1
Circuit #2
Release
Release
Solenoid 1
Solenoid 2
B
B
B
B
-
-
+
+
1 1
2 2
+
-
+
-
TB4
TB5
OUT1
OUT2
Notes:
1.
All End-of-Line Resistors, illustrated in this example, are 4.7KΩ, ½ watt (PN: 71252).
2.
All devices are connected as Class B circuits. For details on connecting as Class A circuits,
refer to "CAC-5X Class A Converter Module" on page 31.
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Input Circuit #1
2-Wire Smoke
Input Circuit #2
2-Wire Smoke
Input Circuit #3
Manual Release/Abort Sw. Combo
Input Circuit #4
Discharge Pressure
Input Circuit #5
Waterflow
B
B
B
B
B
B
B
B
B
-
-
-
-
-
+
+
+
+
4 4
1 1
2 2
3 3
5
+ - + - + - + - + -
FACP Configuration Templates
Output
Circuit #4
Output
Circuit #3
Release
Alarm
Stage
Coded
NAC
+
+
Input Circuit
Supervisory
+
+
+
+
B
B
B
B
-
-
+
+
3 3
4 4
+
-
+
-
TB7
OUT3
OUT4
#6
B
B
-
+
6 6
+ -
TB6
133

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mrp-2002eMrp-2002c

Table of Contents