Silence Inhibited; Coding - Honeywell MRP-2002 Instruction Manual

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Master Programming Level
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the display
will return to NAC Screen #1.
NOTE:
Option will not be available and the display will indicate N/A next to it.

Silence Inhibited

OUTPUT #
1=SILENCEABLE
YES
2=AUTO SILENCE
NO
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board
3=SIL INHIBITED NO
Output for a period of one minute. Resetting the FACP will also be prevented for one minute while
Output Screen #2
the Output programmed for silence inhibit is activated. Pressing 3 while viewing Output Screen #2
will cause a screen to be displayed with the options 1=No Silence Inhibit and 2=1 Min. Silence
Inhibit. Pressing 1 will disable the Silence Inhibit feature while pressing 2 will enable a 1 minute
Silence Inhibit for the selected Output.

Coding

The Coding feature allows the programmer to select the type of output that the main circuit board
OUTPUT #
1=CODING
outputs will generate when activated. Pressing 1 while viewing Output Screen #3 will cause the
following displays to appear:
Output Screen #3
1=STEADY
2=MARCH TIME
3=CALIFORNIA
1=SYNC SYSTEM SENSOR
2=SYNC WHEELOCK
3=SYNC GENTEX
The programmer can select the notification appliance output coding by pressing the number
corresponding to the desired output. The coding selections are:
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
If the Output Circuit has been programmed as a Releasing Circuit, the Auto Silence
CODING
Coding Screen #1
CODING
Coding Screen #4
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second off
Cross-Zone for Release Circuit 1 or Release Circuit 2:
1st zone of a cross-zoned group in alarm causes programmed NAC output to pulse 1 second
on and 1 second off
2nd zone of a cross-zoned group in alarm causes programmed NAC output to pulse ½
second on and ½ second off - Note: if more than two zones are cross-zoned, the programmed
NAC output will continue to pulse ½ second on and ½ second off for each subsequent zone
in alarm, until the final zone in the cross-zoned group goes into alarm
All zones of a cross-zoned group in alarm causes the output programmed as a Releasing
Circuit to perform a release and the programmed NAC output for that Releasing Circuit to
turn on steady
Cross-Zone Pre-Discharge for Release Circuit 1 or Release Circuit 2:
1st zone of cross-zoned group in alarm causes programmed NAC output to turn on steady
CODING
1=TEMPORAL
2=FUTURE USE
3=FUTURE USE
Coding Screen #2
CODING
1=SYNC FARADAY
2=SYNC AMSECO
Coding Screen #5
Programming
CODING
1=CROSS ZONE
2=CROSS ZONE PRE-DIS
3=CROSS ZONE DISCHRG
Coding Screen #3
61