Honeywell MRP-2002 Instruction Manual page 138

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

FACP Configuration Templates
FACP Operation
Input Zone 1 (2-Wire Heat) Activation only:
Output 1 (Release Circuit 1) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 2 (Release Circuit 2) will perform an agent release following a 30 second Pre-
Discharge delay, and remains on until panel reset.
Output 3 (Alarm NAC) will pulse 1 second on, 1 second off until discharge of Release Circuit
1, then turns on steady.
Output 4 (Release Stage Discharge) will turn on steady upon discharge of Release Circuit 1.
Input Zone 2 (2-Wire Heat) Activation only:
Output 1 (Release Circuit 1) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 2 (Release Circuit 2) will perform an agent release following a 30 second Pre-
Discharge delay, and remains on until panel reset.
Output 3 (Alarm NAC) will pulse 1 second on, 1 second off until discharge of Release Circuit
1, then turns on steady.
Output 4 (Release Stage Discharge) will turn on steady upon discharge of Release Circuit 1.
Input Zone 3 (Manual Release) Activation only:
Output 1 (Release Circuit 1) begins agent release and remains on until panel reset.
Output 2 (Release Circuit 2) begins agent release and remains on until panel reset.
Output 3 (Alarm NAC) will turn on steady.
Output 4 (Release Stage Coded) will turn on steady.
Input Zone 4 (Discharge Pressure Switch) Activation only:
Output 3 (Alarm NAC) will turn on steady.
Output 4 (Release Stage Discharge) will turn on steady
Input Zone 5 (Supervisory) Activation only:
No output circuits will be activated. FACP will indicate a supervisory condition.
Input Zone 6 (Supervisory) Activation only:
No output circuits will be activated. FACP will indicate a supervisory condition
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay (Latching) - activation of Input Zone 1 (2-Wire Heat) or Zone 2 (2-Wire Heat) or
Zone 3 (Manual Release) or Zone 4 (Discharge Pressure Switch) will operate Alarm Relay
Trouble Relay (Tracking) - any system trouble will activate the Trouble Relay
Supervisory (Tracking) - activation of Input Zone 5 (Supervisory) or Input Zone 6
(Supervisory), the disabling of Releasing Circuit or any other system supervisory will operate
the Supervisory Relay
138
Template 13: HP CO2 Single Detector
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016